Samsung’s wired controller has its own room sensor, and it’s often in the wrong place: a hallway, a cupboard, next to the cylinder. The heat pump then holds that spot at your target, not the living room.

Room reference fixes this without rewiring anything. Pick a sensor in the room you care about. Your room target becomes that room’s target, and HeatSync gives the unit whatever target makes the controller stop at the right moment:

unit target = your target + (controller's reading − reference reading)

Say you want 21 °C, the lounge sensor reads 18 °C and the cupboard controller reads 25 °C. The offset is +7, so the unit is given 28 °C. It heats until the cupboard reaches 28 °C, which is about when the lounge reaches 21 °C.

Any of these, chosen on Settings → Device → Room reference:

SourceHow
A Bluetooth sensorPair it on the device’s /ble page. The freshest paired reading is used.
MQTTPublish a number to <prefix>/virtual_setpoint/reference (prefix samsung by default), or name any topic in the setting: a bare number, or JSON with a temperature field, so a Zigbee2MQTT sensor’s own topic works as it is.
HTTPPOST /api/virtual-setpoint/reference?value=20.6

“Freshest of Bluetooth and MQTT” takes whichever was heard most recently. A reading older than 15 minutes is ignored.

A third-party thermostat or sensor from Home Assistant

Section titled “A third-party thermostat or sensor from Home Assistant”

A Hive, Nest, Tado or other thermostat’s room reading can be the reference. Republish it with an automation:

automation:
- alias: HeatSync room reference
trigger:
- platform: state
entity_id: sensor.lounge_temperature
- platform: time_pattern
minutes: "/5"
action:
- service: mqtt.publish
data:
topic: samsung/virtual_setpoint/reference
payload: "{{ states('sensor.lounge_temperature') }}"

The time pattern keeps the reading fresh when the temperature holds steady, since a state trigger only fires on a change.

  • Every room target is the reference room’s. The dashboard slider, Home Assistant’s climate entity, the heating schedule, boost and away all set the temperature you want in that room. HeatSync adds the offset before it writes to the unit.
  • The reported temperatures are the reference room’s. /api/live and Home Assistant show your target and the reference reading. The unit’s own values stay in /api/live as unitTargetTemp and unitRoomTemp.
  • Turning the wired remote still works. HeatSync notices the change and takes it as a new target for the reference room.
  • Load compensation uses the reference room’s error.
  • Home Assistant gets two more sensors: Setpoint offset and Reference room temp.

A controller in a cupboard by the unit or its pipework reads warm while the compressor runs. Measured then, the offset would be too big and push the target up just when it’s already heating. So:

  • The offset is only measured once the compressor has been off for 10 minutes. While it runs, the last offset holds.
  • It moves half-way to each new measurement, at most 1 °C at a time, at most every 5 minutes.
  • It’s capped at ±5 °C by default (the Largest offset setting goes up to 8 °C). The unit target stays within 14–32 °C.
  • If the reference goes stale, the offset eases back to 0 and the unit is given your target unchanged.
  • Turning it off writes your target to the unit with no offset, so the unit isn’t left holding a high target.

It needs bus writes on. It only helps when the unit controls to its room sensor: on pure weather compensation the room target has no effect, with or without a reference. The state is on GET /api/virtual-setpoint/status and under the setting.